箱式(shi)變電(dian)站箱殼門應向(xiang)外(wai)開,應有把手、暗閂和(he)鎖,暗(an)閂和(he)鎖應(ying)防(fang)銹(xiu)。變壓(ya)器(qi)室(shi)應以自然通風(feng)為主(zhu),給(gei)出箱內溫度和(he)變壓(ya)器(qi)出力(li)關系(xi)曲線。變壓(ya)器(qi)室(shi)根據需要可(ke)以加裝室(shi)溫監視(shi)裝置和(he)自(zi)啟動的通風(feng)冷(leng)卻裝置,以保證變壓(ya)器(qi)在(zai)規(gui)定(ding)環(huan)境條件下滿(man)負(fu)荷(he)運(yun)行(xing)。變壓(ya)器(qi)應能從(cong)箱頂(ding)部或側門進(jin)出。箱式(shi)變電(dian)站噪音(yin)水(shui)平不應大(da)於(yu)規(gui)定的變壓(ya)器(qi)噪音(yin)水(shui)平。箱殼不論(lun)采(cai)用(yong)金屬(shu)的或非金屬(shu)的材(cai)料(liao),箱體金屬(shu)框(kuang)架均(jun)應(ying)有良(liang)好(hao)的接(jie)地(di),有接(jie)地(di)端子(zi),並(bing)標明(ming)接(jie)地(di)符號。
箱式(shi)變電(dian)站以自然風循環(huan)冷(leng)卻為主(zhu)。因(yin)此(ci),在(zai)其周圍不能違(wei)章堆(dui)物,尤(you)其是變壓(ya)器(qi)室(shi)門不應堵塞(sai),還應(ying)經常清(qing)除百葉(ye)窗(chuang)通風(feng)孔(kong)上附(fu)著物,以確保所(suo)有電(dian)氣設(she)備不超(chao)過(guo)大允許(xu)溫度。低壓(ya)斷(duan)路(lu)器跳(tiao)閘(zha)後(hou),應檢(jian)查跳閘原因後(hou)方可(ke)試(shi)送。若送(song)不成功必須(xu)*尋找故(gu)障(zhang)原因,排(pai)除後(hou)才能送(song)電(dian),防(fang)止(zhi)事(shi)故(gu)擴大(da)。箱式(shi)變壓(ya)器(qi)高壓(ya)配電(dian)室(shi)內應裝設氧(yang)化(hua)鋅(xin)避(bi)雷(lei)器(qi),裝設方式(shi)必須(xu)便(bian)於(yu)試(shi)驗及(ji)拆(chai)裝更換。
箱式(shi)變電(dian)站接(jie)地(di)和零線共用壹(yi)接(jie)地(di)網(wang)。接(jie)地(di)網(wang)壹般在(zai)基礎四(si)角打接(jie)地(di)樁(zhuang),然(ran)後(hou)連(lian)成壹體。箱式(shi)變電(dian)站與接(jie)地(di)網(wang)必須(xu)有兩(liang)處可靠的連(lian)接(jie)。箱式(shi)變電(dian)站運(yun)行(xing)後(hou),應經(jing)常檢查接(jie)地(di)連(lian)接(jie)處,因不松動、無(wu)銹蝕(shi)。定期(qi)測(ce)量接(jie)地(di)電(dian)阻值,接(jie)地(di)電(dian)阻應(ying)不大於(yu)4Ω。箱式(shi)變電(dian)站高壓(ya)配電(dian)裝置中(zhong)的環(huan)網(wang)開關、變壓(ya)器(qi)、避雷(lei)器(qi)等設備應(ying)定期巡(xun)視(shi)維護(hu),發(fa)現(xian)缺陷及(ji)時整修,定期進行(xing)絕(jue)緣預(yu)防(fang)性(xing)試驗。箱式(shi)變電(dian)站停(ting)用時間超(chao)過(guo)3個月(yue),再(zai)投(tou)運(yun)前(qian)應進(jin)行全(quan)項(xiang)預(yu)防(fang)性(xing)試驗。更換無(wu)開斷能力(li)的高(gao)壓(ya)熔斷器,必須(xu)將變壓(ya)器(qi)停(ting)電(dian),操作時要正(zheng)確解除機(ji)械連(lian)鎖,並(bing)使(shi)用絕(jue)緣操(cao)作棒(bang)。箱式(shi)變電(dian)站所(suo)有的進(jin)出線電(dian)纜孔(kong)應(ying)封(feng)堵,防(fang)止(zhi)小動物進(jin)入(ru)造成事(shi)故(gu)。
箱式(shi)變電(dian)站放置的地(di)坪應選(xuan)擇在(zai)較(jiao)高(gao)處,不能放(fang)在(zai)低窪(wa)處,以免雨水(shui)灌入(ru)箱內影響設備運(yun)行(xing)。澆(jiao)制(zhi)混(hun)凝(ning)土(tu)平臺時要在(zai)高(gao)低壓(ya)側(ce)留有空(kong)檔(dang),便(bian)於(yu)電(dian)纜進(jin)出線的敷(fu)設(she)。開挖(wa)地(di)基時,如(ru)遇(yu)垃(la)圾(ji)或腐土(tu)堆積(ji)而成的地(di)面(mian)時,必須(xu)挖(wa)到(dao)實(shi)土(tu),然後(hou)回填較(jiao)好(hao)的土(tu)質(zhi)並(bing)夯(hang)實(shi)後(hou),再(zai)填(tian)三合土(tu)或道渣,確保基礎穩固(gu)。